A primary-design review must prove that ratings, geometry, materials, interfaces, tests and site installation form one coherent MV switchgear system. The following 75-point checklist is a gate-review tool: every item requires objective evidence, an owner and a status—not a verbal “checked.”
Use it at concept, design freeze, pre-type-test/FAT and pre-energisation. Tailor it to the contract and current standards; mark an item N/A only with written justification. It complements—not replaces—the full IEC documents and manufacturer design rules.
How to record the review
| Field | Required entry |
|---|---|
| ID/status | Open, conditionally accepted, accepted or N/A with reason |
| Requirement | Contract/standard clause and revision |
| Evidence | Drawing, calculation, report, test, certificate or site record |
| Owner/due date | Named discipline/person and closure date |
| Risk | Safety, performance, schedule and revalidation consequence |
| Closure | Independent reviewer, date and configuration baseline |
A. Design basis and standards (1–5)
- Design-basis freeze: Is the single controlled document approved for network, ratings, service, environment, layout, operation, maintenance, future extension and responsibility boundaries?
- Standards register: Are exact IEC/IEEE/local editions, amendments, corrigenda, precedence and deviations listed, with current references such as IEC 62271-200:2021+AMD1:2024?
- Service conditions: Are ambient, altitude, humidity/condensation, pollution, solar/corrosive/seismic exposure, frequency and special service conditions quantified rather than labelled “normal” without verification?
- Functional philosophy: Are fixed/withdrawable architecture, compartments, partition class, LSC, IAC, access sides, interlocking and isolation/earthing philosophy aligned with operating procedures?
- Interface control: Are civil, cable, transformer/bus-duct, control/SCADA, earthing, fire/HVAC and pressure-duct interfaces on signed revision-controlled drawings?
B. Network studies and ratings (6–10)
- Voltage/insulation: Are nominal/highest voltage, frequency, insulation level and earthing based on an approved network and insulation-coordination study?
- Continuous current: Do feeder, bus, coupler and neutral/earth current ratings include contingency, harmonics, load profile, ambient and future assumptions?
- Short-circuit duty: Does the IEC 60909 study provide initial symmetrical, peak, duration and fault cases at each section, including motor/generator contribution?
- Switching duties: Are transformer/motor/reactor/capacitor/cable switching, inrush, out-of-phase, restrike/reignition and TRV duties matched to device ratings?
- Auxiliary ratings: Are AC/DC control voltage ranges, ripple, voltage drop, battery autonomy, coil burden and loss-of-supply behaviour defined?
C. Single-line, zones and operating states (11–15)
- Topology: Does the primary single-line match every physical bus section, tee-off, transformer, VT, earth switch and future connection?
- Operating-state table: Are normal, transfer, maintenance, test, emergency and backfeed states analysed for ratings and safety?
- Protection zones: Are CT positions/polarities, breaker-failure zones and blind spots mapped around buses, cables and removable contacts?
- Interlock matrix: Does permitted/prohibited operation cover breaker, disconnect/test position, shutters, earth switches, doors and keys without procedural gaps?
- Isolation points: Can each work zone be isolated, proved dead, discharged and earthed while adjacent required circuits remain safely segregated?
D. Dielectric and insulation coordination (16–20)
- Withstand selection: Are power-frequency, lightning impulse and longitudinal/phase-phase levels coordinated to system surges and protected equipment?
- Clearance: Are phase-earth/phase-phase clearances checked at worst tolerance, altitude, every device position and maximum fault/seismic/thermal displacement?
- Creepage/surfaces: Are material, contamination, condensation and actual application of pollution standards justified—without applying outdoor insulator rules blindly indoors?
- Field control: Are sharp edges, terminals, screens, barriers, triple points, cable stress-control and partial-discharge-sensitive interfaces modelled/qualified?
- Surge protection: Are arrester MCOV/TOV/energy/protective level and lead inductance coordinated with cables, transformers, motors/generators and VT circuits?
E. Continuous-current and thermal design (21–25)
- Loss model: Are conductor AC resistance, proximity/skin, joints, breaker/disconnect, CT/VT and enclosure eddy/hysteresis losses quantified?
- Heat transfer: Are ambient, convection/radiation, compartment coupling, end panels, ventilation recirculation and room/HVAC interfaces represented?
- Material limits: Are permitted temperatures/temperature rises assigned to contacts, insulation, seals, terminals, cables, coils/electronics and accessible surfaces?
- Cooling dependency: If fans/filters are needed, are redundancy, monitoring, failure alarm/derating/trip and maintenance state defined and tested?
- Thermal evidence: Does temperature-rise evidence match worst current path, enclosure, connections, cable quantity and cooling; are model/test margins and variant rules documented?
F. Short-circuit forces and withstand (26–30)
- Current waveform: Are peak asymmetry, RMS/time and source decrement applied to mechanical and thermal checks rather than one kA value?
- Electromagnetic geometry: Are straight spans, bends, tees, risers, parallel paths, cables and return conductors analysed in three dimensions where necessary?
- Load path: Are forces traced through conductors, joints, insulators, brackets, enclosure, shipping splits, base rails and anchors?
- Dynamic response: Are natural modes, damping, transient amplification, contact/slip/plasticity and minimum dynamic clearance addressed?
- Post-test criteria: Do reports inspect joint/contact/support damage, residual deformation, dielectric clearance, resistance and continued operability after short-time/peak tests?
G. Busbars, joints and thermal movement (31–35)
- Bus material/section: Are copper/aluminium grade, conductivity, plating, AC loss, net section at holes and tolerances controlled?
- Joint design: Are contact surfaces, pressure distribution, bolt/preload/washer/lubrication, creep/relaxation and transition-metal corrosion validated?
- Support scheme: Are fixed/sliding supports, expansion joints, flexible links and long-lineup thermal movement unambiguously defined?
- Routing: Are phase geometry, joint count, bends, magnetic loops, tool access and fault-clearance movement optimised together?
- Production QA: Are surface preparation, hardware, calibrated torque/preload, witness marking, resistance baseline and foreign-material exclusion recorded?
H. Switching and instrument devices (36–40)
- Breaker/switch ratings: Are all continuous, interrupting/making, TRV, capacitive/inductive, endurance and operating-sequence duties covered by applicable certificates?
- Withdrawable contacts: Are six-DOF tolerance, engagement/overlap, force, plating, racking signature and position correspondence specified and verified?
- Earthing switch: Is the full making/short-time current path, contact speed/bounce, support and interlocking proven?
- CT/VT/LPIT: Are ratio/class/burden/transient performance, polarity, secondary safety/earthing, fuses/backfeed and physical protection zones coherent?
- Device mounting: Are terminal loads, mass/seismic/transport support, heat, clearances, failure vents and safe replacement/test envelopes verified?
I. Cable interfaces and restraint (41–45)
- Cable schedule: Are exact construction, conductor/screen/armour, diameter/tolerance, installation/final radius, temperature and accessory part numbers frozen?
- Routing: Does a 3D centreline prove bends, straight termination length, phase crossing, tools, replacement and trench/floor tolerance?
- Termination/interface: Are lug/separable interface, load-break/dead-break function, terminal loads, cutbacks, torque/compression and test adapters controlled?
- Cleats: Does IEC 61914 evidence match cable diameter/formation, peak current, spacing, bracket, fasteners and mounting surface?
- Entry/bonding: Are non-magnetic single-core plate needs, glands/seals, screen/armour fault duty, CBCT routing, IP/fire and IAC boundary coordinated?
J. Earthing and fault-return paths (46–50)
- Fault map: Is each credible enclosure, cable, device and earth-switch fault traced to the station grid with its protection clearing/backup time?
- Earth-bus sizing: Are current division, I²t, peak force, net section, joints, branches and external grid leads calculated?
- Protective bonding: Are frames, partitions, doors/removable parts and trucks bonded without relying on paint, hinges, wheels or incidental contact?
- Shipping/site joints: Are earth split links and grid terminals accessible, corrosion-controlled, torque/process-recorded and tested before energisation?
- Functional earths: Are relay/VT/CT/screen/EMC earths kept architecturally correct so small conductors do not become primary fault paths?
K. Enclosure, compartments and internal arc (51–55)
- Compartment architecture: Do partitions/shutters/access rules preserve declared PM/PI, LSC and safe adjacent-compartment conditions?
- IAC definition: Are accessibility sides, current/duration, indicator setup and room/wall/ceiling/floor installation matched to the test report?
- Pressure path: Are compartment volume, flaps, ducts, bends, supports/outlet, cable/brace obstructions and gas transfer controlled?
- Doors/covers: Are latches, hinges, windows, penetrations, fasteners, IP/IK and projectile risks verified under pressure/impact duties?
- Human safety: Are exhaust direction, escape/access, remote operation and residual arc-flash risk assessment treated separately from IAC classification?
L. Structure, seismic, transport and foundation (56–60)
- Enclosure structure: Are thin-sheet buckling, fastener/weld/latch failure, stiffness and functional displacement checked—not von Mises stress alone?
- Seismic: Does IEC 62271-207:2023 evidence state RRS/TRS, damping, axes, configuration, functionality, anchors and site boundary?
- Transport: Are route/environment, packaging, lift/COG, braces/register, impact indicators, storage and receiving quarantine specified?
- Foundation: Are floor elevation/level/flatness/straightness, gauge lengths, supports/shims/grout, anchors and survey method manufacturer-specific?
- Reassembly: Do shipping-split procedures restore frame, main/earth bus, secondary wiring, interlocks, pressure duct and qualification boundary with records?
M. Layout, constructability and maintainability (61–65)
- 3D envelopes: Are electrical, thermal, fault movement, installation, operation, maintenance, mechanism and arc-pressure envelopes checked in every equipment state?
- Panel footprint: Is width/depth/height optimised against total room/aisle/trench/HVAC and lifecycle cost rather than width alone?
- Task analysis: Can qualified personnel perform racking, isolation, earthing, testing, torque and replacement with PPE/tools and adjacent-live restrictions?
- Heavy components: Are lift points, removal path, temporary stability, component mass and ceiling/door/floor capacity documented?
- Future extension: Are electrical/thermal/short-circuit/IAC/seismic end conditions, space, bus joints, cable routes and outage method genuinely feasible?
N. Type-test validity and configuration control (66–70)
- Test matrix: Are all required IEC 62271/product type tests mapped to exact offered functional units, ratings and configurations?
- Reference evidence: Do reports include tested-object drawings/BOM, test values, installation, instrumentation, observations and post-test criteria—not certificate summaries only?
- Extension analysis: Is IEC TR 62271-307:2024 applied test-by-test with quantified influential parameters, validated models and explicit validity limits?
- Substitutions: Do component/material/supplier/firmware/site deviations trigger multidisciplinary review before release, with fleet impact assessed?
- Critical controls: Are dimensions, materials, gas, fasteners, loss, volume, ventilation and processes that preserve validity flagged in PLM/drawings/inspection plans?
O. FAT, SAT, handover and lifecycle (71–75)
- Routine/FAT: Do tests cover primary/earth resistance, dielectric, operation/interlocks, wiring, timing, CT/VT, protection/control and as-built visual/dimensional checks?
- SAT: Are foundation/splits/cables/earth/grid, insulation limits, phasing, trip/close, protection functional, communications and local/remote switching verified safely?
- Baselines: Are breaker timing/travel/coil, contact resistance, thermal, PD/insulation where specified, gas/density and condition-monitoring baselines captured with methods?
- Handover: Are approved as-builts, settings/configurations, certificates/reports, calculations, manuals, spares/tools, training and unresolved punch-list risks transferred?
- Lifecycle plan: Are inspection/maintenance triggers based on duty/condition, post-fault/arc/seismic actions, obsolete parts, modifications and periodic validity/safety review defined?
Review outcome and stop-work criteria
Do not freeze, manufacture or energise while any red issue affects dielectric clearance, fault withstand, protective earth, internal-arc boundary, isolation/interlock, breaker duty, cable constructability or test validity. Conditional acceptance must state the exact temporary condition, risk control, owner, evidence and expiry; it is not a device for moving unresolved engineering into site work.
Minimum final review pack
- approved design basis, standards/deviation and interface registers;
- network, insulation, short-circuit, thermal, mechanical, IAC and earthing studies;
- primary/secondary schematics, layouts, BOM and tolerance models;
- type/routine/FAT/SAT reports and IEC TR 62271-307 dossier;
- civil/foundation, cable, pressure-duct, seismic and transport records;
- closed review log with evidence links, independent approvals and configuration ID.
Independent review sampling
Do not close the checklist by document-presence audit alone. Independently recalculate or trace representative high-risk chains: maximum short-circuit case to support/anchor; cable data to bend/cleat/terminal load; CT ratio/polarity to relay setting/trip; IAC report to installed duct/wall; and type-tested configuration to production BOM. Select at least one end panel, coupler, VT panel, highest-current unit and most congested cable compartment.
- record assumptions and raw values used in the sample;
- verify drawing/BOM/model revisions are mutually consistent;
- follow open interfaces into civil, protection and commissioning packages;
- expand sampling when one discrepancy indicates a systemic control failure;
- require new baseline approval after closure, not isolated redline acceptance.
Core references
- IEC 62271-1:2017+AMD1:2021—Common specifications.
- IEC 62271-200:2021+AMD1:2024—MV metal-enclosed switchgear.
- IEC 60909-0:2026—Short-circuit currents.
- IEC 60865-1:2011—Short-circuit effects.
- IEC 60071-2:2023—Insulation coordination.
- IEC 62271-207:2023—Seismic qualification.
- IEC TR 62271-307:2024—Extension of type-test validity.
Safety note: The checklist supports competent engineering review; it is not permission for unqualified inspection or energised access. Apply the project safety system, manufacturer procedures and governing regulations at every test and work stage.