ANSI 59N and 64 Ground-Fault Protection: Calculated 3V0 vs Broken-Delta Voltage

A structured engineering comparison of 59N and 64 protection, calculated 3V0, broken-delta voltage, VT requirements, settings, grounding methods, and commissioning tests.

Ground-fault voltage protection is often described using several
overlapping terms: 59N, 59G, 64, neutral overvoltage, neutral
displacement, residual voltage, zero-sequence voltage, open delta, and
broken delta
. The confusion begins when an ANSI function number
is treated as if it defined the relay’s physical input.

It does not.

The most important distinction is the measurement
path
:

  1. The relay can calculate residual voltage from three phase-to-ground
    voltages.
  2. The relay can measure residual voltage directly from a broken-delta
    VT circuit or a neutral-to-ground VT.

Both methods may respond to the same earth fault, but their wiring,
scaling, supervision, and failure modes are different. Depending on the
relay manufacturer, either method may be assigned to an element labelled
59N, 59G, 64, residual overvoltage, or neutral displacement. The relay
manual and input-assignment diagram therefore take precedence over the
ANSI label.

Short answer

  • 59N normally means neutral or residual overvoltage
    protection. It operates when the magnitude of a neutral-related voltage
    exceeds a setting.
  • 64 is a broad ground-detection designation. In many
    applications, a voltage-operated 64 element uses a directly measured
    neutral or residual voltage, but 64 is not universally limited to one
    measurement principle.
  • Calculated residual voltage is obtained internally
    as VA + VB + VC = 3V0 and requires three valid
    phase-to-ground voltage inputs.
  • Broken-delta voltage is formed physically by the VT
    secondary windings and is connected to a suitable relay voltage
    input.
  • A broken-delta input is not inherently “59N” or “64.” Its function
    depends on how the specific relay maps the analogue input to its
    protection elements.
  • Neither a basic 59N nor a basic voltage-operated 64 element is
    directional. Directional earth-fault protection normally requires
    current and a polarising quantity.

1. The electrical
quantity behind both methods

For the three phase-to-ground voltage phasors VA, VB, and VC, the
zero-sequence voltage is:

V0 = (VA + VB + VC) / 3

The residual voltage is:

3V0 = VA + VB + VC

In a balanced system, the three phase-to-ground voltage phasors are
displaced by 120 degrees and their vector sum is approximately zero. An
earth fault or neutral displacement introduces zero-sequence voltage, so
the vector sum increases.

The word phasor is essential. The relay does not add
three RMS magnitudes:

|VA + VB + VC| is not equal to |VA| + |VB| +
|VC|

A numerical relay normally samples the voltage waveforms, extracts
the fundamental-frequency phasors, calculates their complex vector sum,
and compares the magnitude with the pickup setting.

V0 and 3V0 are not
interchangeable

Some relays display or set the element in V0, while others use 3V0.
This creates a possible factor-of-three error:

3V0 = 3 × V0

Before calculating any setting, confirm whether the relay parameter
represents:

  • V0;
  • 3V0;
  • raw broken-delta secondary voltage;
  • a primary-referred value; or
  • a per-unit value.

2.
Method A: residual voltage calculated from three phase voltages

The signal path is:

Three phase-to-ground VT inputs → phasor extraction → VA + VB
+ VC → overvoltage pickup → timer → alarm or trip

The operating quantity is normally:

Ures,calc = |VA + VB + VC| = |3V0|

What is required?

  • Three phase-to-ground voltage inputs, not merely two phase-to-phase
    voltages.
  • Correct VT ratio and nominal secondary-voltage configuration.
  • Correct phase identification, phase sequence, and polarity.
  • A valid neutral reference and correct secondary grounding.
  • Healthy VT circuits on all three phases.
  • VT fuse-failure or secondary-MCB supervision where practical.
  • A pickup setting above the maximum standing residual voltage in the
    healthy system.

No dedicated residual-voltage winding is required for this method.
The same three voltage inputs can also support metering, undervoltage,
overvoltage, negative-sequence voltage, synchronism-check, and other
functions.

Why two
line-to-line voltages are insufficient

Zero-sequence voltage is common to all three phase-to-ground voltages
and cancels in a line-voltage subtraction:

VAB = VA − VB

Therefore, true 3V0 cannot be reconstructed from VAB and VBC alone. A
relay may offer a model-specific estimation method using current and
system impedance, but that is an estimated quantity rather than an
independent residual-voltage measurement.

Advantages

  • No separate broken-delta wiring or residual-voltage input is
    needed.
  • Individual phase voltages remain available in metering and
    disturbance records.
  • The three phase-voltage channels can be supervised
    individually.
  • One VT set can support several protection and control
    functions.

Limitations

  • Small VT ratio and phase-angle errors are added as a residual
    quantity.
  • A blown fuse, open circuit, or incorrect phase connection can create
    false residual voltage.
  • The result depends on all three voltage channels being healthy.
  • It cannot be derived directly from a two-VT V–V connection.

3.
Method B: residual voltage measured from a broken delta

A broken-delta circuit uses residual-voltage windings from three VTs.
The windings are connected in series with one corner left open, and the
voltage across the open terminals is proportional to the phasor sum of
the three secondary voltages.

The signal path is:

Residual VT windings → broken-delta output → dedicated relay
voltage input → overvoltage pickup → timer → alarm or trip

The measured quantity is:

Ures,meas = |Ubroken-delta|, proportional to
|3V0|

In a healthy balanced system, the three residual-winding voltages
largely cancel. During an earth fault, the broken-delta output
rises.

Open
delta and broken delta: an important terminology warning

“Open delta” is sometimes used for two different circuits:

  1. A two-VT V–V connection used to obtain
    phase-to-phase voltages.
  2. A three-winding residual or broken-delta connection
    used to obtain voltage proportional to 3V0.

These circuits are not functionally equivalent. A two-VT V–V
connection does not provide a true zero-sequence-voltage measurement. In
this article, broken delta means the residual-voltage
connection in item 2.

What is required?

  • VTs with suitable residual-voltage windings or another approved
    residual-voltage arrangement.
  • Correct series connection and polarity of all residual
    windings.
  • A relay voltage input suitable for the expected broken-delta
    voltage.
  • Correct residual-winding ratio and relay input scaling.
  • Confirmation that maximum earth-fault voltage remains within the
    relay input rating.
  • Secondary fuse or MCB protection and suitable circuit
    supervision.
  • A damping or stabilising resistor when required by the VT
    manufacturer or ferroresonance study.
  • End-to-end commissioning from the VT terminals to the relay
    logic.

Advantages

  • Residual voltage is formed directly by the VT circuit instead of
    being calculated from three relay channels.
  • The residual winding can be designed specifically for earth-fault
    detection.
  • The residual-voltage phasor can often be used as a polarising
    quantity for directional earth-fault protection.
  • It remains available even when the relay has no three
    phase-to-ground voltage channels, provided a compatible residual input
    exists.

Limitations

  • Additional VT windings, wiring, protection, and a relay voltage
    input are required.
  • Incorrect polarity can reduce the output or reverse its angle.
  • An open secondary circuit may make the protection insensitive during
    a real fault.
  • A fuse failure or wiring defect can generate false residual
    voltage.
  • Ferroresonance and resistor thermal duty must be considered.

4. What do 59N and 64
actually mean?

59N

ANSI 59 is an overvoltage function. The suffix N is commonly used for
a neutral-related quantity. A 59N element therefore normally operates
when neutral or residual voltage exceeds its setting.

However, the designation alone does not tell us whether the relay
obtains that voltage by:

  • calculating VA + VB + VC;
  • measuring a broken-delta input;
  • measuring voltage between a machine or transformer neutral and
    ground; or
  • receiving a calculated value through another internal or digital
    signal path.

64

ANSI 64 is a ground detector. Its implementation is
application-dependent and can include voltage-based or other
ground-detection principles. Suffixes and manufacturer terminology may
further distinguish stator ground, rotor ground, restricted earth fault,
neutral displacement, or other schemes.

For this reason, it is unsafe to assume that every 64 element is a
broken-delta overvoltage element. When a relay offers a voltage-operated
64 stage supplied from a residual or neutral-voltage input, its
behaviour may resemble 59N, but its actual input and algorithm must
still be checked.

5. Practical comparison

Engineering question Calculated residual-voltage element Direct residual-voltage element
Typical labels 59N, 59G, residual overvoltage 59N, 59G, 64, ground overvoltage
Measured quantity Internally calculated 3V0 Physical residual or neutral voltage input
Where 3V0 is formed Relay software VT secondary circuit
Required analogue inputs VA, VB, and VC phase-to-ground One suitable residual-voltage input
Broken-delta VT required No Yes, when broken delta is the selected source
CT required for basic overvoltage operation No No
Main scaling risk V0 versus 3V0 and phase-VT ratio Residual-winding ratio and raw input voltage
Main wiring risk Missing phase, fuse failure, phase or polarity error Series polarity, open circuit, fuse failure
Directional by itself No No

The table compares the measurement methods, not
universal ANSI definitions. The exact relay logic may use different
labels.

6. Influence of system
grounding

The usefulness and expected magnitude of residual voltage depend
strongly on the grounding method.

Solidly grounded systems

Earth-fault current is normally high, so overcurrent and differential
protection are usually the principal fault-clearing methods. Residual
overvoltage may be used for supervision, backup, or special zones.

Resistance-grounded systems

Residual voltage can provide sensitive detection of earth faults,
while the grounding resistor limits fault current. Settings must
coordinate with the neutral-grounding resistor protection and feeder
earth-fault elements.

Isolated-neutral systems

During a single earth fault, the neutral shifts and the healthy
phase-to-ground voltages rise. Residual overvoltage is effective for
detecting the presence of a fault, but a non-directional element
generally cannot identify the faulty feeder.

Resonant-grounded systems

Fault current may be very small because a Petersen coil compensates
the network capacitive current. Residual voltage is useful for fault
detection, but feeder selection may require sensitive directional
wattmetric, admittance, transient, or other specialised earth-fault
functions.

7. How to
calculate and select the pickup setting

There is no universal percentage suitable for every installation. The
setting must satisfy both security and sensitivity:

Maximum healthy residual voltage + margin < pickup <
minimum target-fault residual voltage − margin

Use the following process:

  1. Identify the exact relay operating quantity: V0, 3V0, raw secondary
    voltage, primary voltage, or per unit.
  2. Confirm which analogue inputs or calculated signals feed the
    element.
  3. Establish the applicable VT ratios separately for the phase-voltage
    and residual-winding circuits.
  4. Measure or estimate the maximum healthy residual voltage, including
    VT errors and normal system unbalance.
  5. Calculate the minimum residual voltage for the highest-resistance or
    most remote fault that must be detected.
  6. Add security margin for measurement tolerance, frequency variation,
    harmonics, and transient conditions.
  7. Select the delay according to whether the function provides an
    alarm, primary trip, or time-coordinated backup trip.
  8. Define blocking for VT fuse failure, open secondary MCBs,
    maintenance, and invalid measurement conditions.

Scaling the calculated
method

If the phase-to-ground VT ratio is:

nP = primary phase-to-ground voltage / secondary
phase-to-ground voltage

then:

3V0(primary) = nP × 3V0(secondary calculated)

Scaling the broken-delta
method

The broken-delta conversion must be taken from the residual-winding
nameplate data and connection diagram. Do not automatically apply the
normal phase-VT ratio: residual windings are frequently specified with a
different secondary voltage.

8. Numerical example

Assume the relay receives three phase-to-ground voltages containing a
zero-sequence component:

V0 = 8∠30° V secondary

The calculated residual voltage is:

3V0 = 24∠30° V secondary

A calculated residual-overvoltage element therefore measures 24
V.

Assume the broken-delta VT circuit is designed so that the same
primary-system condition produces 24 V at the relay residual-voltage
input. A directly measured element also sees 24 V. With a 20 V pickup,
both elements start.

The two raw readings will only be equal if their scaling is
equivalent. In practice, compare them on a common primary 3V0 or
per-unit base.

9. When directional
protection is required

59N and voltage-operated 64 elements normally indicate that an earth
fault or neutral displacement exists, but they do not determine the
fault direction.

In systems with several feeders, ring operation, parallel sources,
distributed generation, isolated neutrals, or resonant grounding,
selectivity may require a directional earth-fault element such as 67N or
67G. Directional operation requires:

  • a suitable residual or zero-sequence current quantity;
  • a valid polarising voltage, often 3V0 from a calculated or
    broken-delta source;
  • correct current and voltage polarity;
  • a defined characteristic angle or directional method; and
  • commissioning tests that verify both magnitude and angle.

Connecting a broken-delta voltage to a relay does not by itself make
the protection directional.

10. Commissioning tests

Calculated 3V0 path

  1. Apply balanced nominal three-phase voltages and verify that
    calculated 3V0 is close to zero.
  2. Add the same in-phase zero-sequence component to all three voltage
    inputs and verify the expected factor of three.
  3. Test pickup, reset ratio, operating time, and every enabled
    stage.
  4. Simulate each VT fuse or secondary-MCB failure and verify alarm or
    blocking logic.
  5. Confirm phase sequence, phase labels, VT ratio, event records, and
    oscillography.

Broken-delta path

  1. Inject voltage directly into the residual-voltage input and test
    pickup, reset, and timing.
  2. Verify continuity from the VT terminal box to the relay.
  3. Check the polarity and series connection of all residual
    windings.
  4. Confirm the residual-winding ratio and relay scaling.
  5. Test the fuse or MCB supervision logic.
  6. Verify any damping resistor value, connection point, voltage rating,
    and thermal rating.
  7. If the voltage polarises a directional element, test the operating
    and restraining directions.

Cross-checking both methods

When calculated and directly measured residual voltages are both
available, compare them after conversion to a common base:

Mismatch = |3V0(calculated) − K × Ubroken-delta|

An abnormal mismatch can indicate a ratio error, polarity error,
blown fuse, broken wire, or failed voltage channel. The conversion
factor K and the permitted tolerance must be established from the VT
ratios and accuracy classes.

11. Common engineering
mistakes

  • Assuming every 59N element uses calculated VA + VB + VC.
  • Assuming every broken-delta input belongs to a 64 element.
  • Treating ANSI 64 as a universal definition of voltage-operated
    ground protection.
  • Confusing V0 and 3V0 and creating a factor-of-three setting
    error.
  • Adding RMS magnitudes instead of voltage phasors.
  • Expecting true 3V0 from a two-VT V–V connection.
  • Applying the normal phase-VT ratio to a residual winding without
    checking its nameplate.
  • Entering a primary value into a setting expressed in secondary
    volts.
  • Ignoring VT fuse failure, an open residual circuit, or loss of a
    relay voltage channel.
  • Assuming residual overvoltage is feeder-selective or
    directional.
  • Selecting a damping resistor without VT-manufacturer data and system
    studies.

12. Selection guide

Use a calculated residual-voltage element when three
reliable phase-to-ground voltage inputs already exist, the relay
calculation is fully documented, and eliminating additional residual
wiring is desirable.

Use a direct broken-delta measurement when a
dedicated residual winding is provided, the relay has a compatible
input, direct residual measurement is required, or the voltage will also
be used as a polarising quantity.

Use both methods when independent measurement paths,
cross-supervision, or enhanced diagnostics justify the additional
equipment. Remember that two paths using the same primary VT set are not
fully independent.

Use a directional earth-fault function when the
protection must identify the faulty feeder or fault direction rather
than merely detect neutral displacement.

Conclusion

59N and 64 cannot be compared reliably by ANSI number alone. The
decisive questions are:

  • What electrical quantity does the element use?
  • Is residual voltage calculated inside the relay or measured from a
    physical input?
  • Does the relay work with V0, 3V0, or raw broken-delta voltage?
  • Which VT ratio applies?
  • How are voltage-circuit failures supervised?
  • Is simple fault detection sufficient, or is directional selectivity
    required?

Calculated residual voltage and broken-delta voltage are two valid
methods of observing zero-sequence voltage. Their power-system meaning
may be similar, but their measurement paths and engineering requirements
are different. Always verify the relay manual, input matrix, VT
nameplate, wiring diagram, grounding study, and protection-coordination
report before selecting the function and its settings.

References

  1. IEEE
    C37.2-2022 – Device Function Numbers, Acronyms, and Contact
    Designations
    .
  2. IEC 60255-127
    – Functional requirements for over/undervoltage protection
    .
  3. SEL – Protection for
    Unexpected Delta Sources
    , including broken-delta 3V0 and
    voltage-circuit supervision considerations.
  4. SEL – Automatic
    Reconfiguration of Zones for Three-Phase and Spare Transformer
    Banks
    , including comparison of calculated and broken-delta 3V0.
  5. ABB
    – SafePlus 36 Product Catalogue
    , residual-winding ratios and
    damping-resistor application.
LearnSwitchgear

Search the engineering library